Guide to MV Transformers for Tesla Megapack

As the demand for sustainable energy solutions grows, MV transformers for tesla megapackthe Tesla Megapack has emerged as a leading choice for large-scale energy storage projects. Key to the seamless integration of the Megapack is the Medium Voltage (MV) transformer, which plays a critical role in ensuring efficient energy transfer and distribution. This guide aims to provide comprehensive insights into selecting and deploying MV transformers for Tesla Megapack installations in the North American market.

Numerous types of MV transformers are compatible with the Tesla Megapack. Today, our discussion will delve into these options in detail, with a specific focus on the North American context. This article provides detailed information on transformer specifications, datasheets, and specific requirements aligned with the Tesla Megapack's standards.

In the North American market, the oil-immersed pad-mounted transformer stands out as the preferred choice for seamlessly integrating with the Tesla Megapack. Its widespread adoption can be attributed to its ease of installation, exceptional efficiency, and design features meticulously crafted to align with the connection requirements of the Tesla Megapack.

Pad Mounted Transformer Manufacturer

4400 kVA Transformer for Tesla Megapack
4400 kVA Transformer for Tesla Megapack
  • Primary Voltage Ratings: 34.5kV Delta
  • Secondary Voltage Ratings: 480V Grounded Wye
  • H.V. TAP RANGE: +/- 2@ 2.5% HV taps
  • TYPE: Dead Front loop feed HV configuration
  • BIL: 150/30kV
  • Standards: IEEE
  • Application: BESS (Tesla Megapack)
  • Power Rating: 4400kVA
  • Certificate: UL
  • Cooling Method: KNAN
More Detail
4800 kVA Transformer for Megapack
4800 kVA Transformer for Megapack
  • Primary Voltage Ratings: 34.5kV
  • Secondary Voltage Ratings: 480V/277
  • H.V. TAP RANGE: +/- 2@ 2.5% HV taps
  • TYPE: Pad mount
  • BIL: 150/30kV
  • Standards: IEEE, ANSI, NEMA
  • Application: BESS (Megapack)
  • Power Rating: 4800kVA
  • Certificate: UL
  • Cooling Method: KNAN
More Detail
4200kVA Transformer For Tesla Megapack
4200kVA Transformer For Tesla Megapack
  • Primary Voltage Ratings: 13.8kV Delta
  • Secondary Voltage Ratings: 480V Grounded Wye
  • H.V. TAP RANGE: +/- 2@ 2.5% HV taps
  • TYPE: Dead Front loop feed HV configuration
  • BIL: 90/30kV
  • Standards: IEEE
  • Application: BESS (Tesla Megapack)
  • Power Rating: 4200kVA
  • Certificate: UL
  • Cooling Method: KNAN
More Detail
Pad Mounted Transformer Manufacturer

Daelim Transformer stands as a distinguished pad-mounted transformer manufacturer, dedicated to delivering excellence in every aspect of our products and services. Our pad mounted transformers boast a comprehensive range of UL and cUL certifications, guaranteeing strict adherence to rigorous safety standards.

Leverage our extensive experience in executing successful Battery Energy Storage System (BESS) projects throughout North America. Place your trust in Daelim Transformer to furnish bespoke BESS transformer solutions precisely tailored to meet your project requirements with unparalleled precision and reliability. Contact us today to discover how we can empower your sustainable energy initiatives.

Contact Daelim Transformer

Tesla Megapack And MV Transformer Design

For Tesla Megapack, design-specific transformer configurations are required depending on the system's duration. Here are the transformer requirements for both 4-hour and 2-hour Tesla Megapack systems

For Tesla Megapack - 4 Hour System

  • The transformer must have two or four low-voltage outputs.
  • These outputs are situated on both sides of the transformer.
  • Each output is connected to the Tesla Megapack unit accordingly.

In 4-hour systems, double-split transformers are typically employed. These transformers effectively mitigate electromagnetic interference and enhance the quality of power output. Moreover, they facilitate the connection of multiple battery packs. In the event of a malfunction in one battery pack, the power supply to other battery packs remains unaffected.

Reading more: 2500 kVA Split Transformer for Energy Storage

Tesla Megapack and transformer design 4 HR System

Tesla Megapack - 2 Hour System

  • The transformer should feature one low-voltage output.
  • This output is located on one side of the transformer.
  • The output is connected to the Tesla Megapack unit.

Tesla Megapack and transformer design 1 HR System

These specifications ensure that the transformer aligns precisely with the energy storage requirements and setup of the respective Tesla Megapack system duration.

MV Transformer Design Standards For Tesla Megapack

The MV Transformer design shall be outdoor, oil-immersed 3 phase pad mounted type. Transformer characteristics should comply with the latest revisions of ANSI, NEMA, and particularly the relevant IEEE Standards. The transformer design must also hold UL certification.

Standards

  • C57.12.00 - IEEE Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers
  • C57.12.28 - IEEE Standard for Pad-Mounted Equipment--Enclosure Integrity 
  • C57.12.29-2014 - IEEE Standard for Pad-Mounted Equipment--Enclosure Integrity for Coastal Environments
  • C57.12.34 - IEEE Standard Requirements for Pad-Mounted, Compartmental-Type, SelfCooled, Three-Phase Distribution Transformers, 10 MVA and Smaller; High-Voltage, 34.5 kV Nominal System Voltage and Below; Low-Voltage, 15 kV Nominal System Voltage and Below
  • C57.12.90 - IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers
  • C57.154 - IEEE Standard for the Design, Testing, and Application of Liquid-Immersed Distribution, Power, and Regulation Transformers Using High-temperature Insulation Systems and Operating at Elevated Temperatures

Learn more about IEEE C57 Standard

The percent impedance voltage, as measured on the rated voltage connection, shall be per transformer datasheet for target impedances, and the tolerance on the impedance shall be +/- 7.5% of the nominal value.

The guaranteed efficiency shall be per transformer datasheet with a +/- 0.1% allowable deviation in efficiency on individual units but the average for the lot order of transformers shall match the value specified on the datasheet.

The medium voltage bushings shall be 900A deadbreak 40kA Short-time current rating as specified on the transformer datasheet (Section 3). Bushings shall be epoxy/polymer type.

Supplier to notify Tesla if porcelain bushings are offered. Bushings shall be externally removable and be supplied with a removable stud. The transformer shall be provided with six (6) medium voltage loop feed bushings. Medium voltage bushings shall comply with IEEE 386, 2016.

You may enjoy: Guide to Types of High-Voltage Bushings for Pad-Mounted Transformers

Megapack MV Transformer

Megapack MV Transformer
Megapack MV Transformer
  • Transformers shall comply with NEC Article 450.
  • Transformers shall be of dead-front, pad-mount design.
  • Transformer neutral shall not be bonded from primary to secondary. On 4-hour projects, a single transformer neutral bushing shall be brought out in one (1) of the two (2) LV termination cabinets, to prevent unintentional looped connections.
  • Transformer primary terminations shall be configured for loop-feed.
  • Transformers shall have a grounded isolation shield between the high- and low- voltage windings.
Send Inquiry Now
Megapack MV Transformer
Megapack MV Transformer
  • Current Transformers (CTs) shall be mounted internally to the tank under oil to monitor primary current flow through the transformer. MV CTs installed inside the tank shall be 150:1A 5P10 3VA or better accuracy class. Supplier has the option to provide a 5A secondary current rating, pending Tesla approval. If 5A secondary is provided, supplier to revise Slot Z – Current
  • Inputs on the SEL-751 relay from “1” to “5” in digit 15 of the part number. ITI tape wrapped BCTs or equivalent. CT ratio to ensure that full load current is within nominal output of transformer.
Contact Daelim Transformer
Megapack MV Transformer
Megapack MV Transformer
  • Transformer equipped with a load break switch to disconnect transformer from the MV energized circuit while maintaining the rest of the circuit energized. Operating handle shall have provisions to lock the switch on both the open and closed positions.
  • If required on the datasheet the transformer shall be designed to HIGH seismic qualification level per IEEE 693. Frequency modifying devices shall not be allowed without prior approval. 
  • The certified report shall include calculations and summary of the results of the seismic analysis.
Get Price

MV Transformer Low voltage cabinet (4hr system)

  • Transformer LV bushings shall be located in two
    separate LV cabinets in opposing transformer segments.
  • MV Transformer for megapack 4 hour systemLow voltage cabinet shall be provided with tin-plated spade-type bushings. The spacing of the connection holes shall be a standard 1.75” on center 2-hole NEMA spacing, per ANSI C57.12.34 figure 19.
  • Each compartment shall allow for adequate space to install half the parallel set of LV conductors as specified in transformer datasheet. 
  • The quantity of connection holes shall be adequate to install half the parallel set of LV conductors as specified in transformer datasheet
  • Ground bar shall be adequately sized to terminate equipment grounding conductors from Megapacks.
  • LV cabinet shall be supplied with front bolt-on covers or removable doors.
  • Front covers or doors shall be provided with a 2” minimum size Infra-Red (IR) window, outdoor rated for the same environment as the transformer. The window shall be located to allow thermography scans of the transformer electrical connections without the need to opening the cabinet doors or covers. The IR window shall be equipped with a protective cover and security access key.
  • All keys and locks provided should be keyed alike.
  • Install two (2) 1-5/8” Unistrut rails for mounting a field network enclosure on the side of one (1) LV cabinet. The exact dimensions for the rails shall be determined during detailed design.
  • LV cabinet shall have sill panel around the base of the LV cabinet to facilitate cable installation. The dimensions for the openings shall be determined during detailed design. Bottom sill shall provide unobstructed access to perform the cable installation with cables intended to be laid in place.

MV Transformer Low voltage cabinet (2hr system)

  • Transformer LV bushings shall be located in (1) one LV MV Transformer for megapack 2 hour systemcabinet perpendicular to the MV cabinet segment.
  • Low voltage cabinet shall be provided with tin-plated spade-type bushings. The spacing of the connection holes shall be a standard 1.75” on center 2-hole NEMA spacing, per ANSI C57.12.34 figure 19.
  • Each compartment shall allow for adequate space to install all of the parallel sets of LV conductors as specified in transformer datasheet.
  • The quantity of connection holes shall be adequate to install all of the parallel sets of LV conductors as specified in transformer datasheet.
  • Ground bar shall be adequately sized to terminate equipment grounding conductors from Megapacks.
  • LV cabinet shall be supplied with front bolt-on covers or removable doors.
  • Front covers or doors shall be provided with a 2” minimum size Infra-Red (IR) window, outdoor rated for the same environment as the transformer. The window shall be located to allow thermography scans of the transformer electrical connections without the need to opening the cabinet doors or covers. The IR window shall be equipped with a protective cover and security access key.
  • All keys and locks provided should be keyed alike.
  • Install two (2) 1-5/8” Unistrut rails for mounting a field network enclosure on the side of the LV cabinet. The exact dimensions for the rails shall be determined during detailed design.
  • LV cabinet shall have sill panel around the base of the LV cabinet to facilitate cable installation. The dimensions for the openings shall be determined during detailed design.
  • Bottom sill shall provide unobstructed access to perform the cable installation with cables intended to be laid in place.

Accessory Cabinets

Accessory CabinetsA liquid level gauge, pressure gauge, and dial type thermometer each with dry type alarm contacts must connect to a separate NEMA 4 or NEMA 4X rated enclosure outside of the LV or MV compartments. The location of this enclosure must be such that, when open, the gauges can be read from grade level without the use of a ladder. Pressure gauges shall usePSI for units of measurement. Temperature gauges shall use degree Celsius for units of measurement & be installed in a dry, threaded well to allow removal of gauge for testing or replacement without spilling oil.

The transformer shall have an externally mounted SEL-751 relay (P/N: SEL-751001A0X1A0XA11C10 inside a NEMA 4 or NEMA 4X box. The relay shall be mounted on a swing-out sub panel. Transformer manufacturer shall include digital input connections to the relay from all transformer gauges (level, pressure, and temperature). Each additional relay connection points shall be wired to terminal blocks inside the enclosure to allow for future use without the need to connect to the relay directly.

All control wiring shall be stranded, tinned copper SIS wire, minimum #14 AWG, insulated for 600V AC, 90°C.

¾” metallic conduit chase shall be factory installed between the MV cabinet and SEL relay enclosure.

No more than two wires shall be terminated on any one terminal block or connection. Wire splicing is not permitted.

Terminal blocks shall be phenolic or polyamide block rated 600V and not less than 20A.

Identify each terminal on each block with a permanent designation.

Refer to Tesla provided FNE + RIB panel drawings.

Oil sampling port shall be external to any cabinet (MV or LV) and provided with a dedicated lockable cover. Preferred sampling location is near the LV Cabinet.

Learn more about Pad Mounted Transformer Accessories

Megapack 4800 kVA Transformer DATA SHEET–4HR Projects

Data Sheet

DESCRIPTION UNIT DATA
Tesla Part Number P/N 1943161-0X-B
Enclosure rating ANSI Outdoor
Operating Frequency Hz 60
Capacity kVA 4800
Cooling Class - KNAN
Impedance @ nominal Voltage on Base Rating Z% 7.5% ±7.5%
Efficiency @ 100% of Maximum MVA 75 Rating % >=99.0%
Total losses at Max. MVA cannot exceed % 1.00%
Windings 2-3 2
Rated Voltage of MV Terminals (Nominal) kV 34.5
Rated Voltage of LV Terminals (Nominal) V 480/277
Basic Impulse Level MV Terminals (BIL) kV 150
Basic Impulse Level LV Terminals (BIL) kV 30
MV Winding Config Delta/wye Delta
LV Winding Config Delta/wye Wye
Loop or Radial System Design - Loop Feed
Livefront or Deadfront - Deadfront
Connection LV Terminals (Cable or Bus Duct) Cable, Compression lugs
Oil/Fluid Type Less Flammable Fluid
Type of Material Used in Coils - Al or Cu

Standard Features and Accessories

  • Nameplate
  • Dial-type thermometer
  • Liquid level gauge
  • Pressure-vacuum gauge
  • 1 in drain valve with sample valve
  • Pressure relief valve
  • 1 in upper fill/filter press connection
  • Color: RAL 9016 Traffic White
  • Medium Voltage Switch: Pad Mount type, pad-lockable
  • SEL-751
  • Internal CT’s
  • NC alarm contacts on temperature, liquid level, and pressure/vacuum gauges and pressure relief device
  • Seismic anchoring as per IEEE 693
  • LV busbar on segments 2 and 4 (sides of the transformer)
  • The structural support base for ground screws or similar support
  • Structural base maximum anchoring/support points: 4
  • IR window MV and LV Cabinets

Megapack 4800 kVA Transformer DATA SHEET–2HR Projects

Data Sheet

DESCRIPTION UNIT DATA
Tesla Part Number P/N 1943164-0X-B
Enclosure rating ANSI Outdoor
Operating Frequency Hz 60
Capacity kVA 4800
Cooling Class - KNAN
Impedance @ nominal Voltage on Base Rating Z% 7.5% ±7.5%
Efficiency @ 100% of Maximum MVA 75 Rating % >=99.0%
Total losses at Max. MVA cannot exceed % 1.00%
Windings 2-3 2
Rated Voltage of MV Terminals (Nominal) kV 34.5
Rated Voltage of LV Terminals (Nominal) V 480/277
Basic Impulse Level MV Terminals (BIL) kV 150
Basic Impulse Level LV Terminals (BIL) kV 30
MV Winding Config Delta/wye Delta
LV Winding Config Delta/wye Wye
Loop or Radial System Design - Loop Feed
Livefront or Deadfront - Deadfront
Connection LV Terminals (Cable or Bus Duct) Cable,Compression lugs
Oil/Fluid Type Less Flammable Fluid
Type of Material Used in Coils - Al or Cu

Reading more about the 4800 kVA Transformer

 

Standard Features and Accessories

  • Nameplate
  • Dial-type thermometer
  • Liquid level gauge
  • Pressure-vacuum gauge
  • 1 in drain valve with sample valve
  • Pressure relief valve
  • 1 in upper fill/filter press connection
  • Color : RAL 9016 Traffic White
  • Medium Voltage Switch: Pad Mount type, pad lockable
  • SEL-751
  • Internal CT’s
  • NC alarm contacts on temperature, liquid level, and pressure/vacuum gauges and pressure relief device
  • Seismic anchoring as per IEEE 693
  • LV busbar on segments 2 (1 side of the transformer)
  • The structural support base for ground screws or similar support
  • Structural base maximum anchoring/support points: 4
  • IR window MV and LV Cabinets

4400 kVA Pad mounted transformer for Megapack 2 XL

Specifications

  • Power Rating: 4400kVA
  • Primary Voltage: 34.5kV Delta
  • Secondary Voltage: 480V Grounded Wye             
  • Phase: 3-Phase (4 Wire)
  • Frequency: 60 HZ
  • Temperature Rise: 65 °C @ 46°C Ambient
  • Cooling Class: KNAN
  • %IZ: 6.50% +/- 7.5% @4400kVA
  • BIL HV: 150kV
  • BIL LV: 30kV          

Learn more about the 4400kVA Transformer                                                             

Transformer design

  • To accommodate two Tesla Megapack 2XL’s on each side of the transformer, for a total of four Megapack 2XL’s.
  • To meet the latest revisions of the following battery storage manufacturer Tesla transformer requirements:
  • Tesla Megapack – Above Grade Transformers. Transformer to be designed to accommodate the 4-hour Megapack configuration.
  • Tesla Megapack 2XL Design and Installation Manual
  • Appropriately for the conditions of use including solar duty, ambient temperatures, and harmonic loading (k-factor of 2 or higher)
  • To meet all applicable UL and IEEE standards including C57.12.00, C57.12.28, C57.12.34, C57.12.70, C57.12.80, C57.12.90, and C57.18.10
  • To be pad mount, outdoor, UL nameplated
  • With natural ester insulating fluid
  • To be sealed-tank construction
  • As dead-front loop feed HV configuration
  • For step-down, bi-directional operation
  • With continuous windings without splices
  • With an electrostatic shield between the HV and LV windings and an externally accessible ground shield bushing
  • With a NEMA 3R termination cabinet
  • With a five position tap changer with +/- 2@ 2.5% HV taps
  • With Bay-O-Net or internal expulsion and coordinated back-up current-limiting primary fuse protection
  • One-piece 600A HV bushings in HV connection cabinet
  • With a HV two position load break oil-immersed rotary switch
  • LV Spade terminals to accommodate horizontal lug spacing of 2.0”
  • With a 14-hole grounding bus plate and will accept NEMA two-hole ground lugs in the LV compartment
  • HV Compartment to have a standard NEMA two-hole ground pad
  • With liquid thermometer, liquid-level and pressure/vacuum gauges with Form C alarm contacts prewired to terminal blocks in externally accessible enclosure
  • With a Schrader-type valve
  • With a cover-mounted automatic pressure relief valve as required to prevent tank rupture
  • Oil drain, fill, and oil sample and pressure relief valves
  • With a nitrogen blanket
  • With seismic anchoring provisions for the site indicated above and for 3/4" hardware
  • With RAL-7035 color finish in accordance with C57.12.18-2014 and spare touch-up paint
  • Rated for continuous operation

Reading on: The Impact of Impedance on Transformer Design

Transformer Factory Acceptance Test

Factory Acceptance Test shall include all tests required by IEEE C57.12.90 specifically the as listed below designated as “Routine” and “Design”.

Transformer Factory Acceptance Test

Tests requested by Tesla. Reference: IEEE C57.12.00-2015, Table 17 No Design
Resistance measurements of all windings on the rated voltage tap Yes Yes
Ratio tests on the rated voltage connection as listed on the nameplate Yes No
Polarity and phase relation tests on the rated voltage connection Yes No
No-load losses and excitation current at 100% of rated voltage and at rated power frequency on the rated voltage tap connections Yes No
No-load losses and excitation current at 110% of rated voltage and at rated power frequency on the rated voltage tap connections No Yes
Impedance voltage and load loss at rated current and rated frequency on the rated voltage connection, and at the tap extremes of the first unit of a new design Yes No
Operation tests of all devices Yes No
Control (auxiliary) and cooling consumption losses, if applicable. Yes No
Temperature rise at minimum and maximum ratings of the first unit of a new
design
No Yes
Dissolved gas in oil analysis Yes No
Audible sound level No Yes
Winding insulation resistance Yes No
Lightning impulse Yes Yes
Low frequency - Voltage Applied Yes No
Low frequency - Voltage Induced Yes No
Partial discharge test No Yes
Lifting and moving devices No Yes
Oil Leaks Yes No
Current Transformer Factory Acceptance Testing Yes No
Turns ratio & phase angle accuracy test. Yes No
Winding resistance test Yes No
Polarity test Yes No
Excitation test Yes No
Insulation resistance test Yes No
Relay acceptance test Yes No
Power up relay Yes No
Check wiring from CT to each relay input to ensure phase & polarity is correct Yes No
Check wiring from each alarm contact to the relay through the SEL HMI program Yes No

(*) Note: The routine column refers that all units shall be tested. The design column refers that only 1 unit shall be tested.

You may enjoy: How to test a power transformer?

Medium Voltage cabinet

Medium voltage enclosures shall be in ANSI Outdoor or greater enclosure.

Conform to ANSI C57.12.28, with doors that are capable of being removed from the hinges during transformer service.

Be provided with LOTO capabilities for disconnect switch.

All keys and locks provided should be keyed alike.

Doors shall be provided with a 2” minimum size Infra-Red (IR) window, outdoor rated for the same environment as the transformer. The window shall be located to allow thermography scans of the transformer electrical connections without the need to opening the cabinet doors or covers. The IR window shall be equipped with a protective cover and security access key.

Deadbreak bushings to be mounted at a minimum of 4 feet from transformer base.

Equipment Marking and Labeling

Signage shall be provided on all electrical equipment in accordance with Applicable Law, including NEC and NFPA 704 requirements.

Signage shall be weather-proof, corrosion-proof, UV-stabilized, and fade-resistant and

shall be capable to last the duration of the minimum design life.

Signs shall be attached using non-corrosive materials suitable to meet the Minimum Design Life.

Transformer shall have an engraved permanent identification label visible and readable from a distance of 48 inches that provides the unique identification number as indicated on the electrical drawings and in the LOTO procedure.

All equipment identifications shall be unique, and match provided design documents.

Equipment identifications shall be consistent across all references.

Permanent labels shall be suitable for wet locations and rated for UV resistance if exposed.

Structural Support Base

The transformer shall be provided with a steel structural support to allow direct transformer installation on top of ground screws, helical piles, driven piles or similar type of foundations.

Drawings shall indicate locations for anchor bolts.

Conclusion

The pad-mounted transformer serves as the ideal companion for the Tesla Megapack in BESS projects. If you find yourself uncertain about selecting the right transformer for your Tesla Megapack BESS project, drop Daelim Transformer a line! We are committed to helping you acquire the transformer necessary to energize your BESS project effectively. Trust in Daelim Transformer to provide the expertise and support you need to make your project a success.

pad mounted transformer

Related Article

Daelim Transformer Custom 1500 kVA Pad Mounted Transformer for Canada

As a professional pad mounted transformer manufacturer & supplier, Daelim Transformer is committed to meeting standards such as ANSI/IEEE, CSA, DOE, and NEMA, offering customized solutions. Here, we present a case of a 1500 kVA pad mounted transformer tailored for the Canadian market.

Pad Mounted Transformer for BESS System 4.0 MVA in Riverside County, California

Today, Daelim Transformer is proud to introduce a pad-mounted transformer for a 4.0 MVA Battery Energy Storage System (BESS) project located in Riverside County, California. The transformer is meticulously crafted to comply with the specifications outlined in the California Electrical Code Article 450.

2600 kVA Pad Mounted Transformer for Cryptocurrency Mining

Daelim Transformer successfully provided three customized 2600 kVA pad mounted transformers to power a state-of-the-art cryptocurrency mining facility in Texas, USA. Our transformers were meticulously designed to meet the unique demands of the mining operation, ensuring seamless power distribution with unwavering reliability and efficiency.

2000 kVA Pad Mounted Transformers for Canadian Utility

Daelim Transformer is pleased to announce its contribution to a utility project in Toronto, Canada, involving the supply of two units 2000 kVA pad mounted transformers. These transformers are integral to enhancing the power infrastructure in the region. The project demands adherence to CSA standards, with a stringent delivery deadline of 10 weeks to meet the urgent needs of the client.

2 MVA Pad Mounted Transformer for Utility

Behold the backbone of Canada's utility infrastructure—the 2MVA pad mounted transformer. With a primary voltage of 4160Grdy/2400V and a secondary voltage of 800GrdY/461V, this transformer stands as a testament to efficiency and reliability in power distribution. Crafted in strict accordance with CSA standards and CAN/CSA802.1 energy efficiency guidelines, it embodies the pinnacle of engineering excellence.

2550 kVA Pad Mounted Transformer For Data Center in Mexico, Missouri

Today, we're excited to showcase Daelim Transformer's involvement in a project supplying four 2550 kVA pad mounted transformers tailored for a data center located in Mexico, Missouri. Data centers, known for their substantial power demands, require reliable solutions to ensure seamless operation during peak electricity usage.

Quote Now


Please Write your message, ask for price, we will reply you soon, thanks