150kV 120 MVA 150 MVA Power Transformer


  • Primary Voltage Ratings: 150kV
  • Secondary Voltage Ratings: 11kV
  • H.V. TAP RANGE: 150*±8*1.25%
  • CONNECTION TYPE: YNd11
  • TYPE: Conservator type transformer
  • Standards: IEC
  • Application: Gas Turbine Project
  • Power Rating: 120MVA/150MVA
  • Cooling Method: ONAN/ONAF

The 150 kV 120 MVA / 150 MVA power transformer, designed for a Gas Turbine Project, features a 2-winding core type with copper windings and a conservator. It offers 120 MVA capacity in self-cooling mode and up to 150 MVA with fan assistance. Equipped with a 17-step MR Brand on-load tap-changer, it includes various accessories such as oil level and temperature gauges, a Buchholz relay, and surge arresters. Daelim Transformer provides customized solutions and quick, efficient service to meet your project needs.


Quote Now
None

The 150 kV 120 MVA / 150 MVA power transformer is designed for a Gas Turbine Project. It is a 2-winding, core-type oil transformer with a conservator, featuring copper windings. It has single-stage cooling, with a capacity of 120 MVA in self-cooling mode and up to 150 MVA with the fan active. This transformer is equipped with a renowned MR Brand on-load tap-changer on the HV side with 17 steps.

Rating:

Rated capacity at ONAF

  • HV: 150MVA(Continuous)
  • LV: 80MVA

Rated capacity at ONAN

  • HV: 120MVA(Continuous)
  • LV: 60MVA

Tap-Changer:MR TAP CHANGER

  • Brand: MR
  • Motor Drive Unit: MR ED 100
  • Automatic Voltage Regulator: MR Tapcon
  • Type: On-Load Tap Changer
  • Number of Steps: 17
  • Position of Tapings: HV
  • Voltage Regulation Range: ±8 × 1.25%

Tank:

  • Material: Steel Q235
  • Type: Bell Type
  • Vacuum Withstanding: 133 Pa
  • Tank and Conservator Pressure: 133 Pa
  • Terminal Boxes: 1 Unit

Accessories and Gauges:120 mva transformer

HV Bushings: 3

  • HV Neutral Bushing: 1
  • LV Bushings: 3
  • Current Transformers on HV Bushings (R, S, T): 600/1, Class 0.2, 50 VA
  • Current Transformer on Neutral: 600/1, Class 5P20, 50 VA
  • On-Load Tap Changer: 1 Unit
  • Oil Level Gauges: 2 - CEDASPE
  • Winding Temperature Gauge: 1 - QUALITROL
  • Liquid Temperature Gauges: 2 - QUALITROL
  • Large Pressure Relief Device: 1
  • Buchholz Relay: 1 - EMB
  • Rapid Pressure Rise Relay: 1
  • Conservator with Diaphragm & Silica Gel Breather: 2 - CEDASPE
  • Oil Sampling Device: 1
  • Draining Valve: 1
  • Filter Valve: 1
  • Lifting Lugs & Jacking Pads: Yes
  • Transformer Name Plate, Valve Plate & Diagram Plate: Yes
  • Protective Relay for OLTC: Yes (MR)
  • Anti-Vibration Pads: Yes
  • OLTC Operation Mechanism: Yes
  • Surge Arresters for HV: 3

Daelim Transformer specializes in manufacturing power transformers tailored to your project needs. Whether you are an investor, contractor, EPC, or end-user, we can promptly provide all necessary parameters, documentation, drawings, and pricing. Efficient communication, fast delivery, and high-quality competitive pricing will help you secure your project and achieve rapid returns. Contact Daelim Transformer now to advance your project.

DOE
AS
GOST