3000 kVA Substation Transformer
- Primary Voltage Ratings: 11kV , 44 kV, 4.16 kV, 13.8 kV, 24.94 kV, 34.5 kV
- Secondary Voltage Ratings: 415V, 600v, 400V, 480v
- H.V. TAP RANGE: 10175V-11275V
- CONNECTION TYPE: Dyn11
- TYPE: SF-3000/11/0.415
- BIL: 30-95kV
- Standards: AS/NZS 60076, IEC60076-1, IEC60076-3
- Application: Crypto Mining
- Power Rating: 3000 kVA, 3 MVA
This is a 3000 kVA substation transformer designed to meet Australian standards, specifically for use in cryptocurrency mining operations in Australia. It features a side outlet design for both high and low pressure. The transformer operates at a high voltage of 11kV, which is stepped down to a low voltage of 415V. Its primary function is to provide stable and continuous power supply to the mining machines, ensuring uninterrupted operation. Compliance with Australian standards guarantees the transformer's safety, efficiency, and reliability within the mining industry. Daelim Transformer is a professional manufacturer of transformers with extensive project experience in Australia, New Zealand, and other countries. We have offered numerous transformer services for mines, power stations, industrial, and commercial sectors in Australia and New Zealand. Our services encompass distribution transformers below 35kV, as well as HV power transformers exceeding 66kV.
Quote Now
3000 kVA(3MVA) Substation Transformer
3000 kVA Substation Transformer
The SL-3000/11/0.415 transformer is a 3-phase substation transformer designed for use in Australia and conforms to the AS/NZS 60076, IEC60076-1, and IEC60076-3 standards. These standards ensure that the transformer meets the necessary safety and performance requirements for the Australian market.
The transformer has a primary voltage of 11000V and a secondary voltage of 415V, which are typical voltage levels for distribution transformers in Australia.
The high-voltage bushing of the transformer is of the dead-front type, which means that it is designed to be fully enclosed and insulated, minimizing the risk of accidental contact with live parts.
The transformer features a terminal box for connecting indicators and gauges. This box allows for convenient monitoring and measurement of various parameters during operation.
To adhere to Australian standards, the transformer utilizes capital and small letters A(a), B(b), and C(c) markings for high and low voltage phases, and the grounding terminal is marked with N(n) to indicate the neutral connection.
Contact Daelim Transformer3000 kVA Transformer Accessories
Here's the list of accessories for the SL-3000/11/0.415 substation transformer.
3 HV bushings: These are high-voltage bushings with a voltage rating of 25kV and a current rating of 630A. They are used for connecting the transformer to the high-voltage power source.
4 LV bushings: These are low-voltage bushings with a voltage rating of 1kV and a current rating of 500A. They are used for connecting the transformer to the low-voltage distribution system.
2 handholes: These are access points with covers or doors that allow maintenance personnel to access the interior components of the transformer for inspection or repairs.
One pressure relief device: This device is designed to relieve excessive internal pressure in the transformer to prevent damage or explosion in case of abnormal operating conditions.
Get Price3000 kVA Transformer Accessories
One liquid level gauge: This gauge is used to monitor the level of insulating liquid (such as oil) inside the transformer tank, ensuring proper cooling and insulation.
One thermometer: The thermometer is used to measure the temperature of the transformer, providing important information for monitoring and controlling the operating conditions.
One vacuum pressure gauge: This gauge measures the vacuum pressure inside the transformer tank, which can provide information about the integrity of the sealing and insulation system.
One throat flanges HV & LV: The throat flange is a component used for connecting the transformer's high-voltage and low-voltage bushings to the associated cables or conductors.
One 5-position tap changer: This tap changer allows for the adjustment of the transformer's turns ratio by selecting different tapping points on the winding, enabling voltage regulation.
One marshaling box: The marshaling box is a junction box used for organizing and connecting various electrical control and monitoring circuits associated with the transformer.
Contac Daelim Transformer44 kV 3000 kVA(3900 kVA) Substation Transformer
The S-3000-3990/44-0.6 transformer is designed and produced according to CSA standards specifically for the Canadian market.
The transformer has a high voltage (HV) rating of 44kV, which represents the primary voltage level. The low voltage (LV) rating is 600V, representing the secondary voltage level.
The power rating of the transformer is specified as 3000kVA for KNAN (Kilovolt-Ampere Natural Air Natural) cooling and 3900kVA for ONAF (Oil Natural Air Forced) cooling. This indicates the capacity of the transformer to handle power at different cooling methods. The main technical specifications are as follows
HV | 44000 Delta volts | Oil weight | 2150 kg |
LV | 600 Y/346 Volts | Total weight | 8800 kg |
KNAN Rating | 3000 kVA | HV | 46200V |
KNAF | 3900 kVA | 45100V | |
Frequency | 60Hz | 44000V | |
HV BIL | 250 kV | 42900V | |
LV BIL | 30 kV | 41800V |
The S-3000-3990/44-0.6 transformer feature
- Cooling Method: The transformer uses ONAN/ONAF cooling, which stands for Oil Natural Air Natural/Oil Natural Air Forced. This means that the transformer primarily relies on the natural circulation of the insulating oil for cooling, but it also has provisions for forced air cooling if necessary.
- Conductor Material: The high-voltage (HV) winding and low-voltage (LV) winding of the transformer are both made of copper (Cu) conductors.
- Insulating Oil: The transformer is filled with Type II mineral oil, which contains less than 2 parts per million (ppm) of polychlorinated biphenyls (PCBs). Type II mineral oil is commonly used as an insulating and cooling medium in transformers.
- Liquid Level and Temperature: The transformer's liquid level is maintained at 270 mm below the top of the highest manhole flange at a temperature of 25°C. The liquid level changes by 10 mm for every 10°C change in the average liquid temperature.
- Tank Design: The transformer tank is designed to withstand a complete vacuum and can also handle an internal pressure of up to 7 pounds per square inch (psi). This ensures the structural integrity and safety of the transformer during operation.
- De-Energized Tap Changers: It is important not to energize the transformer from any voltage source when the de-energized tap changers are being operated. This precaution helps prevent any potential electrical hazards during tap-changing operations.
- Pressure Limits: The transformer is designed to operate within pressure limits of 10 psi positive (above atmospheric pressure) and 8 psi negative (below atmospheric pressure). This ensures the transformer can operate safely within the specified pressure range.
- Energy Efficiency: The energy efficiency of the transformer complies with the CAN/CSA-C802.3 standard, which is based on the CSAC88 requirements. This indicates that the transformer meets the specified energy efficiency standards set for its operation.
You may enjoy: Pad Mounted Transformer
Other 3000 kVA Substation Transformer
4.16 kV 3000 kVA Transformer
The SL-3000/4.16/0.4 is a Canadian standard transformer according to the CSA C88-M16 standard. Applied in the Canadian market.The following is some main parameter information about SL-3000/4.16/0.4 transformer:
- Model: SL-3000/4.16/0.4
- Standard: CSA C88-M16 (Canadian standard)
- Primary Voltage: 41600V
- Secondary Voltage: 400V
- Capacity: 3000 kVA
- Connection Group: Dyn1
- Outlet Structure: High and low voltage side outlets
- Cover: Sealed cover
- Insulating Liquid: Mineral oil, Class A
- Cooling Method: ONAN (Oil Natural Air Natural)