400 MVA Transformer
- Primary Voltage Ratings: 330kV
- Secondary Voltage Ratings: 150kV
- TYPE: Autotransformer
- BIL: 950/550kV
- Standards: DSTU EN 60076-1, GOST
- Power Rating: 400MVA
- Cooling Method: ONAN/ONAF/OFAF
The 400 MVA transformer, designed for temperate climates and outdoor use, operates effectively at elevations up to 1000 meters and temperatures from -40°C to +45°C. It features a high voltage rating of 330 kV and medium voltage of 165 kV, with a cooling system of ONAN/ONAF/OFAF. The transformer includes advanced safety and monitoring systems, a robust cooling and maintenance setup, and a reliable control cabinet. It ensures a high efficiency of 99.797%, with a service life of at least 30 years and an MTBF of 25,000 hours.
Quote Now
The 400 MVA transformer is a three-phase, oil-immersed autotransformer with forced air and oil circulation cooling. It is a double-winding unit with a rated capacity of 400,000 kVA and voltage classes of 330 kV (HV) and 165 kV (LV). Designed for temperate climates and suitable for outdoor installation, it operates efficiently at altitudes of up to 1,000 meters and in ambient temperatures ranging from -40°C to +45°C.
Key Specifications
- Rated Capacity: 400,000 kVA
- High Voltage (HV): 330 kV
- Medium Voltage (MV): 165 kV
- Winding Connection: Yna
- Longest Permissible Current: 979 A
- Cooling System: Three-stage ONAN/ONAF/OFAF
- Transformer Efficiency (PEI): 99.797%
Insulation and Voltage Ratings
- Full Wave Lightning Impulse (LI):
- HV Winding: 950 kV
- MV Winding: 550 kV
- Chopped Wave Lightning Impulse (LIC):
- HV Winding: 1050 kV
- MV Winding: 600 kV
- AC Withstand Voltage (LTAC):
- HV Winding: 395 kV (ph-ground), 525 kV (ph-ph)
- MV Winding: 230 kV (ph-ground), 275 kV (ph-ph)
- Neutral Insulation Class: 35 kV
- AC Neutral Input Test Voltage: 85 kV
Cooling and Maintenance
- Oil Preservation System: Elastic membranes air-bag type
- Tank Design: Bell type with lower connector and additional oil sump
- Cooler Group: Shut-off valves with visual indicators and easy maintenance access
Safety and Monitoring
- Gas Relay: Two-float design with separate 'alarm' and 'trip' settings
- Oil and Winding Temperature Indicators: Equipped with contacts for monitoring
- Pressure Relief Valve: Includes actuation signalling contacts
- Control Cables: Routed in stainless steel sleeves for protection against mechanical damage and sunlight
Additional Features
- Control Cabinet: IP55 protection, automatic temperature maintenance, dual power sources, and LED lighting
- Voltage Control Device: Vacuum diverter switch of OLTC with a 1250 A rated current
- Tap Changer Range: ±8.4% to +7.2% with 8 steps
Reliability and Longevity
- Mean-Time-Between-Failures (MTBF): Minimum 25,000 hours
- Operational Service Life: Minimum 30 years
This 400 MVA autotransformer combines advanced technology with rigorous standards to ensure exceptional reliability and efficiency for high-demand power applications.