4600 kVA Inverter Duty Transformer


  • Primary Voltage Ratings: 33 000 V
  • Secondary Voltage Ratings: 480 V
  • H.V. TAP RANGE: -5 % to +5 %
  • TYPE: Inverter Duty Transformer
  • Standards: AS/NZS
  • Application: Tesla Megapack 2 XL
  • Power Rating: 4600 kVA
  • Cooling Method: ONAN

The 4600 kVA Inverter Duty Transformer boasts rugged construction, high overload capability, and low noise and vibration levels. Purpose-built for energy storage applications, it excels under high-frequency and transient load conditions. Specifically tailored for the Australian market, this transformer complies meticulously with AS standards.


Quote Now
Rating 4.6 MVA / 2.3 MVA / 2.3 MVA
Phase 3
Frequency 50 Hz
No. of windings  3
Nominal primary voltage 33 kV
Nominal secondary voltage 480 V
Nominal tertiary voltage 480 V
Vector group Dyn11yn5
Impedance 7.5 % )
Transformer efficiency 99% (minimum)
Operating mode Single

Location

Degree of protection

Harmonics compliance

Method of cooling

Insulation level - primary 

Power frequency withstand voltage-primary 

Lightning impulse withstand voltage - primary 

Outdoor

IP56

As per AS/NZS 

Natural Convection

36 kV (rms)

70 kV (rms)

200 kV (peak)

Contact Daelim Transformer for special requirements

Oil level low (alarm) With externally readable gauge
Oil level trip Yes
Oil temperature high (alarm) With externally readable gauge
Oil Temperature trip Yes
Winding temperature RTD Yes
Pressure relief device  Yes
Winding temperature high (alarm) With externally readable gauge
Winding temperature trip Yes
Main tank Buchholz relay Yes
Type Off load tap changer at primary winding
Tapping Range -5 % to +5 %
Principal tap 33,000 V
Number of tap positions 5
Change per step 2.5 %
Temperature (max/min) 50 / 0 degC
Average Summer Dry Bulb temperature 30.4 degC
Relative humidity (max/min) 20 - 65 %
Maximum Design Humidity 100%
Site elevation < 50 m
Proximity to the Sea 10 km
Atmospheric corrosivity category  C4
Wind Region  D
Terrain Category  1
Pollution level IV - Very Heavy

The 4600 kVA transformer features a low-voltage double-split structure, with its capacity divided into two equal parts of 2300 kVA each. These segments can operate independently or simultaneously, each connected to a Tesla Megapack 2 XL separately.

Double-split transformers facilitate electrical isolation between the two inverters, effectively reducing electromagnetic interference and circulating current between the branches. Furthermore, they ensure that the AC outputs of the inverters are filtered individually, resulting in minimal output current harmonics and enhanced power quality.

In the event of a short circuit in one branch, the transformer not only effectively limits the short-circuit current but also maintains the voltage of the other branch at a certain level, thus ensuring uninterrupted user operations.

Hence, it is evident that double-split step-up transformers are the preferred choice for large-scale photovoltaic power generation and energy storage projects.

With extensive experience in large-scale photovoltaic power generation and energy storage projects, Daelim Transformer can meet all technical requirements associated with such projects. Additionally, our professional team can significantly save on time costs, and our fast delivery times ensure the smooth completion and delivery of projects. Contact us now to discuss your next project.